7.4.4.44 Pset_ProtectiveDeviceBreakerUnitI2TCurve

PSET_TYPEDRIVENOVERRIDE / IfcProtectiveDevice

Protective Device Breaker Unit I2 TCurveA coherent set of attributes representing a curve for let-through energy of a protective device. Note - A protective device may be associated with different instances of this pSet providing information related to different basic characteristics
保護装置の通電エネルギーの曲線を表す一連のプロパティセット。 注記-保護装置は、根本的な特性に関連付けられた提供されたプロパティの情報は、 異なる実態に関連しているかもしれません。
Properties

PSD-XML

NameTypeDescription
VoltageLevel P_ENUMERATEDVALUE / IfcLabel / PEnum_VoltageLevels
Voltage LevelThe voltage levels for which the data of the instance is valid. More than one value may be selected in the enumeration.
電圧レベル保護装置が作動する電圧レベルを選択。 [U230,U400,U525,U690,U1000,その他,不明,無]
NominalCurrent P_SINGLEVALUE / IfcElectricCurrentMeasure
Nominal CurrentThe nominal current that is designed to be measured. A set of nominal currents in [A] for which the data of this instance is valid. At least one value shall be provided. Any value in the set shall not exceed the value of the UltimateRatedCurrent associated with the same breaker unit.
定格電流定格電流[A]を少なくても1つ値をセットしなければならない。 セット内の任意の値の値を超えてはならない。 定格電流は、同じブレーカ部に関連付けられている。
BreakerUnitCurve P_TABLEVALUE / IfcElectricCurrentMeasure / IfcReal
Breaker Unit CurveA curve that establishes the let through energy of a breaker unit when a particular prospective current is applied. Note that the breaker unit curve is defined within a Cartesian coordinate system and this fact must be asserted within the property set: (1) Defining value: ProspectiveCurrent: A list of minimum 2 and maximum 16 numbers providing the currents in [A] for points in the current/I2t log/log coordinate space. The curve is drawn as a straight line between two consecutive points. (2) Defined value: LetThroughEnergy: A list of minimum 2 and maximum 16 numbers providing the let-through energy, I2t, in [A2s] for points in the current/I2t log/log coordinate space. The curve is drawn as a straight line between two consecutive points.
遮断機曲線適用された電流と通過する遮断機のエネルギーを示した曲線 (1)定義値:ProspectiveCurrent(固有電流): 電流/I2tで示される最小2から最大8のリストで電流[A]を定義します。 カーブが連続する2つの点を結ぶ直線として描かれています。 (2)定義値:LetThroughEnergy: 電流/I2tで示される最小2から最大8のリストで通過エネルギー電流[[A2s]を定義します。 カーブが連続する2つの点を結ぶ直線として描かれています。