7.5.4.14 Pset_ChillerTypeCommon

PSET_TYPEDRIVENOVERRIDE / IfcChiller

Chiller Type CommonChiller type common attributes.
Properties

PSD-XML

NameTypeDescription
Reference P_SINGLEVALUE / IfcIdentifier
ReferenceReference ID for this specified type in this project (e.g. type 'A-1'), Also referred to as "construction type". It should be provided as an alternative to the name of the "object type", if the software does not support object types and no classification reference to a recognized classification system used.
IFC4.3.0.0 DEPRECATION  The Reference property is deprecated and shall no longer be used, use attribute Name on the relating type instead.
参照当該プロジェクトで定義する形式の参照ID(例:A-1)、承認された分類に存在しないときに使用される。
Status P_ENUMERATEDVALUE / IfcLabel / PEnum_ElementStatus
StatusStatus of the element, predominately used in renovation or retrofitting projects. The status can be assigned to as "New" - element designed as new addition, "Existing" - element exists and remains, "Demolish" - element existed but is to be demolished, "Temporary" - element will exists only temporary (like a temporary support structure).
EtatEtat de l'élément, utilisé avant tout pour les projets de rénovation et réaménagement. L'état assigné peut être "Nouveau" - l'élément prévu pour du neuf, "Existant" - l'élément existait et est maintenu, "Démoli" - l'élément existait mais doit être démoli/supprimé, "Provisoire" - l'élément existera à titre provisoire seulement (comme un support structurel par exemple).
状態要素(主にリノベーションまたは改修プロジェクトにおいて)の状態。 状態は、「新規(New)」-新しく追加される要素。「既存」-要素は存在し、かつ残りもの。「破壊」-要素は存在したが、廃棄されるもの。「一時的」-一時的に存在する要素(一時的にサポートしている構造のようなもの)。
ChillerCapacity P_SINGLEVALUE / IfcPowerMeasure
Nominal CapacityNominal cooling capacity of chiller at standardized conditions as defined by the agency having jurisdiction.
PuissanceNominalePuissance froid nominale du groupe froid aux conditions standardisées telles que définies par l'organisation faisant autorité.
NominalEfficiency P_SINGLEVALUE / IfcPositiveRatioMeasure
Nominal EfficiencyNominal object efficiency under nominal conditions.
EfficacitéNominaleEfficactié nominale du groupe froid sous les conditions nominales.
NominalCondensingTemperature P_SINGLEVALUE / IfcThermodynamicTemperatureMeasure
Nominal Condensing TemperatureChiller condensing temperature.
TemperatureCondensationNominaleTempérature de condensation du groupe froid.
NominalEvaporatingTemperature P_SINGLEVALUE / IfcThermodynamicTemperatureMeasure
Nominal Evaporating TemperatureChiller evaporating temperature.
TempératureEvaporationNominaleTempérature d'évaporation du groupe froid.
NominalHeatRejectionRate P_SINGLEVALUE / IfcPowerMeasure
Nominal Heat Rejection RateSum of the refrigeration effect and the heat equivalent of the power input to the compressor.
CoefficientEvacuationNominaleChaleurSomme de l'effet de réfrigération et de la chaleur équivalente à la puisssance absorbée par le compresseur.
NominalPowerConsumption P_SINGLEVALUE / IfcPowerMeasure
Nominal Power ConsumptionNominal total power consumption.
ConsommationPuissanceNominalePuissance de consommation totale nominale.
CapacityCurve P_TABLEVALUE / IfcThermodynamicTemperatureMeasure / IfcPowerMeasure
Capacity CurveChiller cooling capacity is a function of condensing temperature and evaporating temperature, data is in table form, Capacity = f (TempCon, TempEvp), capacity = a1+b1Tei+c1Tei^2+d1Tci+e1Tci^2+f1TeiTci. This table uses multiple input variables; to represent, both DefiningValues and DefinedValues lists are null and IfcTable is attached using IfcResourceConstraintRelationship and IfcMetric. Columns are specified in the following order: 1.IfcPowerMeasure:Capacity 2.IfcThermodynamicTemperatureMeasure:CondensingTemperature 3.IfcThermodynamicTemperatureMeasure:EvaporatingTemperature
CourbePuissancePuissance frigoifique du groupe froid qui est une fonction de la température de condensation et de la température d'évaporation, les informations sont sous la forme d'un tableau, Puissance = f(TempCon,TempEvp), puissance = a1+b1Tei+c1Tei2+d1Tci+e1Tci2+f1TeiTci. Ce tableau utilises plusieurs entrées variables; pour la représenter, DefiningValues et DefinedValues sont pour les deux nulles et IfcTable est attachée en utilisant IfcPropertyConstraintRelationship et IfcMetric. Les colonnes sont indiquées dans l'ordre suivant:
  1. IfcPowerMeasure: Capacity
  2. IfcThermodynamicTemperatureMeasure: CondensingTemperature
  3. IfcThermodynamicTemperatureMeasure: EvaporatingTemperature
CoefficientOfPerformanceCurve P_TABLEVALUE / IfcThermodynamicTemperatureMeasure / IfcReal
Coefficient Of Performance CurveChiller coefficient of performance (COP) is function of condensing temperature and evaporating temperature, data is in table form, COP= f (TempCon, TempEvp), COP = a2+b2Tei+c2Tei^2+d2Tci+e2Tci^2+f2TeiTci. This table uses multiple input variables; to represent, both DefiningValues and DefinedValues lists are null and IfcTable is attached using IfcResourceConstraintRelationship and IfcMetric. Columns are specified in the following order: 1.IfcPositiveRatioMeasure:CoefficientOfPerformance 2.IfcThermodynamicTemperatureMeasure:CondensingTemperature 3.IfcThermodynamicTemperatureMeasure:EvaporatingTemperature
CourbeCOPCoefficient de Performance (COP) du groupe froid qui est une fonction de la température de condensation et de la température d'évaporation, les informations sont sous la forme d'un tableau, COP = f(TempCon,TempEvp), COP = a2+b1Tei+c2Tei2+d2Tci+e2Tci2+f2TeiTci. Ce tableau utilises plusieurs entrées variables; pour la représenter, DefiningValues et DefinedValues sont pour les deux nulles et IfcTable est attachée en utilisant IfcPropertyConstraintRelationship et IfcMetric. Les colonnes sont indiquées dans l'ordre suivant:
  1. IfcPowerMeasureCapacity
  2. IfcThermodynamicTemperatureMeasure: CondensingTemperature
  3. IfcThermodynamicTemperatureMeasure: EvaporatingTemperature
FullLoadRatioCurve P_TABLEVALUE / IfcPositiveRatioMeasure / IfcNormalisedRatioMeasure
Full Load Ratio CurveRatio of actual power to full load power as a quadratic function of part load, at certain condensing and evaporating temperature, FracFullLoadPower = f ( PartLoadRatio).
CourbeFonctionnementPleineChargeRapport entre la puissance instantanée et la puissance à pleine charge comme fonction quadratique de charge partielle, pour une certaine température de condensation et une température d'évaporation, FracFullLoadPower= f (CoefficientChargePartielle)