Name | Type | Description |
OccupancyDiversity |
P_SINGLEVALUE
/
IfcPositiveRatioMeasure
|
| Occupancy Diversity | Diversity factor that may be applied to the number of people in the space.
|
| 居住者の在室率 | 室内居住者の在室率。
|
|
OutsideAirPerPerson |
P_SINGLEVALUE
/
IfcVolumetricFlowRateMeasure
|
| Outside Air Per Person | Design quantity of outside air to be provided per person in the space.
|
| 1人あたりの外気量 | 1人あたりの外気量の設計値。
|
|
ReceptacleLoadIntensity |
P_SINGLEVALUE
/
IfcHeatFluxDensityMeasure
|
| Receptacle Load Intensity | Average power use intensity of appliances and other non-HVAC equipment in the space per unit area.(PowerMeasure/IfcAreaMeasure).
|
| 単位面積あたり事務機器の平均電力消費量 | 単位面積あたり事務機器など非空調設備の平均電力消費量。
(PowerMeasure/IfcAreaMeasure)
|
|
AppliancePercentLoadToRadiant |
P_SINGLEVALUE
/
IfcPositiveRatioMeasure
|
| Appliance Percent Load To Radiant | Percent of sensible load to radiant heat.
|
| 放射熱のうち顕熱分の割合 | 放射熱のうち顕熱分負荷の割合。
|
|
LightingLoadIntensity |
P_SINGLEVALUE
/
IfcHeatFluxDensityMeasure
|
| Lighting Load Intensity | Average lighting load intensity in the space per unit area (PowerMeasure/IfcAreaMeasure).
|
| 照明負荷率 | 単位面積あたり照明機器の平均電力消費量。
(PowerMeasure/IfcAreaMeasure)
|
|
LightingPercentLoadToReturnAir |
P_SINGLEVALUE
/
IfcPositiveRatioMeasure
|
| Lighting Percent Load To Return Air | Percent of lighting load to the return air plenum.
|
| リタン空気への照明機器の放熱率 | 照明機器からリタン空気(天井裏)への放熱率。
|
|