7.4.4.82 Pset_TransformerTypeCommon

PSET_TYPEDRIVENOVERRIDE / IfcTransformer

Transformer Type CommonAn inductive stationary device that transfers electrical energy from one circuit to another.
1つの回路からもう一つへ電気エネルギーを移す電磁誘導装置。
Change log
ItemSPFXMLChangeDescription
IFC4 Addendum 2 Technical Corrigendum 1 4.0.2.1
    Pset_TransformerTypeCommon
      EfficiencyCurveADDED
      RadiativeFractionADDED
IFC4x1 Final 4.1.0.0
    Pset_TransformerTypeCommon
      EfficiencyCurveDELETED
      RadiativeFractionDELETED
IFC4X3_ADD2 to IFC4X4_draft
    Pset_TransformerTypeCommon
      NumberOfPhasesADDED
Properties

PSD-XML

NameTypeDescription
Reference P_SINGLEVALUE / IfcIdentifier
ReferenceReference ID for this specified type in this project (e.g. type 'A-1'), Also referred to as "construction type". It should be provided as an alternative to the name of the "object type", if the software does not support object types and no classification reference to a recognized classification system used.
IFC4.3.0.0 DEPRECATION  The Reference property is deprecated and shall no longer be used, use attribute Name on the relating type instead.
参照当該プロジェクトで定義する形式の参照ID(例:A-1)、承認された分類に存在しないときに使用される。
Status P_ENUMERATEDVALUE / IfcLabel / PEnum_ElementStatus
StatusStatus of the element, predominately used in renovation or retrofitting projects. The status can be assigned to as "New" - element designed as new addition, "Existing" - element exists and remains, "Demolish" - element existed but is to be demolished, "Temporary" - element will exists only temporary (like a temporary support structure).
状態要素(主にリノベーションまたは改修プロジェクトにおいて)の状態。 状態は、「新規(New)」-新しく追加される要素。「既存」-要素は存在し、かつ残りもの。「破壊」-要素は存在したが、廃棄されるもの。「一時的」-一時的に存在する要素(一時的にサポートしている構造のようなもの)。
PrimaryVoltage P_SINGLEVALUE / IfcElectricVoltageMeasure
Primary VoltageThe voltage that is going to be transformed and that runs into the transformer on the primary side.
第1電圧変圧器の1次側に伝送される電圧。
SecondaryVoltage P_SINGLEVALUE / IfcElectricVoltageMeasure
Secondary VoltageThe voltage that has been transformed and is running out of the transformer on the secondary side.
第2電圧変圧器の2次側へ出力される電圧。
PrimaryCurrent P_SINGLEVALUE / IfcElectricCurrentMeasure
Primary CurrentThe current that is going to be transformed and that runs into the transformer on the primary side.
第1電流変圧器の1次側に伝送される電流。
SecondaryCurrent P_SINGLEVALUE / IfcElectricCurrentMeasure
Secondary CurrentThe current that has been transformed and is running out of the transformer on the secondary side.
第2電流変圧器の2次側へ出力される電流。
PrimaryFrequency P_SINGLEVALUE / IfcFrequencyMeasure
Primary FrequencyThe frequency that is going to be transformed and that runs into the transformer on the primary side.
第1周波数変圧器の1次側に伝送される周波数。
SecondaryFrequency P_SINGLEVALUE / IfcFrequencyMeasure
Secondary FrequencyThe frequency that has been transformed and is running out of the transformer on the secondary side.
第2周波数変圧器の2次側に出力される周波数。
PrimaryApparentPower P_SINGLEVALUE / IfcPowerMeasure
Primary Apparent PowerThe power in VA (volt ampere) that has been transformed and that runs into the transformer on the primary side.
第1電力変圧器の1次側に伝送される電力(VA: アンペア)。
SecondaryApparentPower P_SINGLEVALUE / IfcPowerMeasure
Secondary Apparent PowerThe power in VA (volt ampere) that has been transformed and is running out of the transformer on the secondary side.
第2電力変圧器の2次側へ出力される電力(VA: アンペア)。
MaximumApparentPower P_SINGLEVALUE / IfcPowerMeasure
Maximum Apparent PowerMaximum apparent power/capacity in VA (volt ampere).
最大電力皮相電力/容量 の最大値 (VA:アンペア)。
SecondaryCurrentType P_ENUMERATEDVALUE / IfcLabel / PEnum_SecondaryCurrentType
Secondary Current TypeA list of the secondary current types that can result from transformer output.
第2電流タイプ変圧器より出力される第2電流の種類の一覧。
ShortCircuitVoltage P_SINGLEVALUE / IfcComplexNumber
Short Circuit VoltageA complex number that specifies the real and imaginary parts of the short-circuit voltage at rated current of a transformer given in %.
短絡電圧%で与えられる変圧器の定格電流における短絡電圧の実数と虚数を定義する複素数。
RealImpedanceRatio P_SINGLEVALUE / IfcRatioMeasure
Real Impedance RatioThe ratio between the real part of the zero sequence impedance and the real part of the positive impedance (i.e. real part of the short-circuit voltage) of the transformer. Used for three-phase transformer which includes a N-conductor.
インピーダンス実部比率零相インピーダンスと正相インピーダンス(例.短絡電圧の実部)の間の比率。N-コンダクターを含む三相トランスのために使用。
ImaginaryImpedanceRatio P_SINGLEVALUE / IfcRatioMeasure
Imaginary Impedance RatioThe ratio between the imaginary part of the zero sequence impedance and the imaginary part of the positive impedance (i.e. imaginary part of the short-circuit voltage) of the transformer. Used for three-phase transformer which includes a N-conductor.
インピーダンス虚部比率零相インピーダンスと正相インピーダンス(例.短絡電圧の虚部)の間の比率。N-コンダクターを含む三相トランスのために使用。
TransformerVectorGroup P_ENUMERATEDVALUE / IfcLabel / PEnum_TransformerVectorGroup
Transformer Vector GroupList of the possible vector groups for the transformer from which that required may be set. Values in the enumeration list follow a standard international code where the first letter describes how the primary windings are connected, the second letter describes how the secondary windings are connected, and the numbers describe the rotation of voltages and currents from the primary to the secondary side in multiples of 30 degrees. D: means that the windings are delta-connected. Y: means that the windings are star-connected. Z: means that the windings are zig-zag connected (a special start-connected providing low reactance of the transformer); The connectivity is only relevant for three-phase transformers.
IsNeutralPrimaryTerminalAvailable P_SINGLEVALUE / IfcBoolean
Is Neutral Primary Terminal AvailableAn indication of whether the neutral point of the primary winding is available as a terminal (=TRUE) or not (= FALSE).
中性点第1ターミナルがあるかどうか一次巻線の中性点がターミナルの場合は(=TRUE)、違う場合は(= FALSE)として表示する
IsNeutralSecondaryTerminalAvailable P_SINGLEVALUE / IfcBoolean
Is Neutral Secondary Terminal AvailableAn indication of whether the neutral point of the secondary winding is available as a terminal (=TRUE) or not (= FALSE).
中性点第2ターミナルがあるかどうか二次巻線の中性点がターミナルの場合は(=TRUE)、違う場合は(= FALSE)として表示する
NumberOfPhases P_SINGLEVALUE / IfcCountMeasure Number of phases that the equipment operates on.

Link to this page  Link to this page