6.2.4.15 Pset_DistributionPortTypeCable

PSET_OCCURRENCEDRIVEN / IfcDistributionPort / CABLE

Distribution Port Type CableCable port occurrence attributes attached to an instance of IfcDistributionPort.
IfcDistributionPortオブジェクトに設定される電力ポートに関する属性情報。
Change log
ItemSPFXMLChangeDescription
IFC4 Addendum 1 4.0.1.0
    Pset_DistributionPortTypeCableMODIFIEDInstantiation changed from IfcDistributionPort/ELECTRICAL to IfcDistributionPort/CABLE.
Properties

PSD-XML

NameTypeDescription
ElectricalConnectionType P_ENUMERATEDVALUE / IfcLabel / PEnum_DistributionPortElectricalType
Connection TypeThe physical port connection: ACPLUG: AC plug DCPLUG: DC plug CRIMP: bare wire
接続タイプ物理ポート接続:
  • ACPLUG: AC プラグ
  • DCPLUG: DC プラグ
  • CRIMP: 裸線
ConnectionSubtype P_SINGLEVALUE / IfcLabel
Connection SubtypeThe physical port connection subtype that further qualifies the ConnectionType. The following values are recommended: ACPLUG: A, B, C, D, E, F, EF, G, H, I, J, K, L, M DIN: Mini3P, Mini4P, Mini5P, Mini6P, Mini7P, Mini8P, Mini9P DSub: DA15, DB25, DC37, DD50, DE9, DE15 EIAJ: RC5720 HDMI: A, B, C RADIO: IEEE802.11g, IEEE802.11n RJ: 4P4C, 6P2C, 8P8C SOCKET: E-11, E-12, E-14, E-17, E-26, E-27, E-39, E-40 TRS: TS_Mini, TS_SubMini, TRS_Mini, TRS_SubMini
接続サブタイプ物理ポート接続のサブタイプ。接続タイプ以外の情報を設定する場合に使用。下記の値を設定:
  • ACプラグ: A, B, C, D, E, F, EF, G, H, I, J, K, L, M
ConnectionGender P_ENUMERATEDVALUE / IfcLabel / PEnum_DistributionPortGender
Connection GenderThe physical connection gender.
接続ジェンダー形状的な接続ジェンダー(オス、メス、その他、未知、未設定)。
ConductorFunction P_ENUMERATEDVALUE / IfcLabel / PEnum_ConductorFunctionEnum
Conductor FunctionIndicates function of the conductors to which the load is connected. Where L1, L2 and L3 represent the phase lines according to IEC 60446 notation (sometimes phase lines may be referenced by color [Red, Blue, Yellow] or by number [1, 2, 3] etc). Protective Earth is sometimes also known as CPC or common protective conductor. Note that for an electrical device, a set of line conductor functions may be applied.
電線種類電気負荷と連結する電線種類。
CurrentContent3rdHarmonic P_SINGLEVALUE / IfcPositiveRatioMeasure
Current Content3rd HarmonicThe ratio between the third harmonic current and the phase current.
第3高調波電流と相電流の比第3高調波電流と相電流の比率。
Current P_BOUNDEDVALUE / IfcElectricCurrentMeasure
CurrentThe actual current and operable range.
電流実電流と動作可能範囲。
Voltage P_BOUNDEDVALUE / IfcElectricVoltageMeasure
VoltageThe actual voltage and operable range.
電圧実電圧と動作可能範囲。
Power P_BOUNDEDVALUE / IfcPowerMeasure
PowerThe actual power and operable range.
電力実電力と動作可能範囲。
Protocols P_LISTVALUE / IfcIdentifier
ProtocolsFor data ports, identifies the protocols used as defined by the Open System Interconnection (OSI) Basic Reference Model (ISO 7498). Layers include: 1. Physical; 2. DataLink; 3. Network; 4. Transport; 5. Session; 6. Presentation; 7. Application. Example: 3:IP, 4:TCP, 5:HTTP
プロトコルOSIのオープンシステム相互接続用基本プロトコル(ISO 7498):
  1. 物理層; 2.データリンク層; 3. ネットワーク層; 4. トランスポート層; 5. セッション層; 6.プレゼンテーション層 ; 7. アプリケーション層. 例: 3:IP, 4:TCP, 5:HTTP
HasConnector P_SINGLEVALUE / IfcBoolean Indicate whether the wire pair end point is terminated with a connector or not.
IsWelded P_SINGLEVALUE / IfcBoolean Indicates whether the wire pair end point is joined to another wire pair end point by means of a welded junction.